FP2SH CPU
|
A high-performance model for high-speed operation Scanning time of 1ms for 20k steps. With an operating speed at the top of its class, super high-speed processing is made possible. The result is a dramatically decreased tact time and high-speed device. Large programming capacity of up to 120k steps Large programming capacities of 60k and 120k are available, depending on the model. Combine modules like building blocks I/O units, intelligent units, power supply units and backplanes can be used together for the FP2 and the FP2SH. I/O units can be located anywhere on the backplane. Optional small PC card is also available The small PC card is available for programming backup or data memory expansion. This allows you to process great amounts of data. Built-in comment and real-time clock functions These functions, optional with the FP2, are built right into the FP2SH.
|
 |
 |
| Performance specifications |
|
 |
| PLC type |
FP2-C2, FP2-C2P, FP2-C3P |
| Inputs/outputs |
Central: max. 1600 (with 25 modules) Locally expanded: max. 8172 (via MEWNET-F or S-LINK) |
| Memory |
RAM (EPROM or FROM and IC memory card optional) |
| Program memory |
FP2-C2, FP2-C2P: 60,000 steps FP2-C3P: 120,000 steps |
| Number of instructions |
|
| Basic instructions |
95 |
| High-level instructions |
434 |
| Operating speed |
0.03µs per basic instruction |
| Internal relay (R) |
14,192 |
| Memory |
Timer/counter (T/C) |
3,072 |
| Data register (DT) |
0,240 words |
| File register (FL) |
32,765 words x 3 banks |
| Master control relay (MCR) |
256 (1st programme: 256 points / 2nd programme: 256 points) |
| Jump labels (JMP + LOOP) |
256 (1st programme: 256 points / 2nd programme: 256 points) |
Max. main memory programme steps |
1,000 |
| Number of subroutines |
100 |
| Interrupt programme |
1 |
| Time interrupt |
0.5ms to 1.5s |
| Other functions |
Test run operation, forced input/output, interrupt processing, batch conversion, function for multiple instructions in RUN mode, calendar time, computer link and modem control via the TOOL and COM port, IC card, 2MB SRAM, flash-EEPROM, ROM operation, comment input function |
|
 |
 |
|
Power supply modules
|
|
| P / N | Voltage | Rating (at 5V side) | | FP2-PSA1 | 100 - 120V AC | 2.5A | | FP2-PSA2 | 200 - 240V AC | 2.5A | | FP2-PSA3 | 100 - 240V AC | 5A | | FP2-PSD2 | 24V DC | 5A |
|
 |
 |
|
Input modules
|
|
| P / N | I/O Number | Voltage | Connection | | FP2-X16D2 | 16 | 12 - 24V DC | Terminal | | FP2-X32D2 | 32 | 24V DC | Connector | | FP2-X64D2 | 64 | 24V DC | Connector |
|
 |
 |
|
Output modules
|
|
| P / N |
I/O Number |
Voltage |
Connection |
| FP2-Y6R |
6 relay |
250V AC / 5A |
terminal |
| FP2-Y16R |
16 relay |
250V AC / 2A |
terminal |
| FP2-Y16P |
16 transistor PNP |
12-24V DC / 0.5A |
terminal |
| FP2-Y16T |
16 transistor NPN |
12-24V DC / 0.5A |
terminal |
| FP2-Y32P |
32 transistor PNP |
12-24V DC / 0.1A |
connector |
| FP2-Y32T |
32 transistor NPN |
12-24V DC / 0.1A |
connector |
| FP2-Y64P |
64 transistor PNP |
12-24V DC / 0.1A |
connector |
| FP2-Y64T |
64 transistor NPN |
12-24V DC / 0.1A |
connector |
|
 |
 |
|
I/O mixed modules
|
|
|
| FP2-XY64D2T |
FP2-XY64D2P |
| Input |
32 |
| Voltage |
24V DC |
| Response time OFF-> ON |
0.3ms or less |
| Output |
32 |
| I/O number |
Transistor NPN |
Transistor PNP |
| Voltage |
5 to 24V DC |
| Rating |
0.1A (12-24V DC) |
50mA (5V DC) |
|
 |
 |
|
Analogue modules
|
|
| Analogue input modules |
| P/N |
FP2-AD8X |
FP2-AD8VI |
FP2-RTD |
| Input range |
+/-100mV, +/-10V, 1-5V, thermocouples, RTD |
+/-10V, 1-5V, +/-20mA, 4-20mA |
Pt100, JPt100, JPt1000 |
| Conversion speed |
500µs/ch voltage 20ms/ch temp. |
500µs/ch |
20ms/ch |
| Accuracy |
+/-0.1% Voltage +/-0.3% V temp. |
+/-1.0% |
+/-0.3% |
| |
| Analogue output module |
| P/N |
FP2-DA4 |
| Outputs |
4 |
| Output range |
-10V to +10V, 0 to 20mA |
| Conversion speed |
500µs/ch |
| Accuracy |
+/-1.0% (at 0 to 55°C) |
Twenty types of input range such as voltage and temperature sensor are selectable and available for various connection devices (FP2-AD8X). RTD device and thermocouple can be directly connected (FP2-AD8X, FP2-RTD).
|
 |
 |
|
Positioning modules
|
|
For system-integrated 2- and 4-axis path control. Maximum 4Mpps command yields high-speed and high-precision positioning. 0.005ms high-speed drive reduces tact time. Feedback pulse count function makes output pulse counting possible for encoders, etc. JOG positioning control supports a wide range of applications. | Product number | Specifications | | FP2-PP21 | Transistor output, 2 axes | | FP2-PP41 | Transistor output, 4 axes | | FP2-PP22 | Line driver output, 2 axes | | FP2-PP42 | Line driver output, 4 axes |
|
 |
 |
|
High-speed counter and pulse I/O modules
|
|
| High-speed counter modules |
| Counter |
4 channels, max. 200kHz |
| Interrupt input |
8 points |
| Calculation range |
32-bit |
| |
|
|
| P / N |
FP2-HSCP |
FP2-HSCT |
| Input type |
PNP |
NPN |
| |
|
|
| Pulse I/O modules |
| Counter |
4 channels, max. 200kHz |
| Interrupt input |
8 points |
| PWM output |
4 points: 1Hz to 30kHz |
| Pulse output |
4 points: 100kHz |
| |
|
|
| P / N |
FP2-PXYP |
FP2-PXYT |
| Output type |
PNP |
NPN |
|
 |
 |
|
FP2 Multi-wire link module and S-Link module
|
|
| FP2 multi-wire link module FP2-MW |
- PLC link function:
Enables data to be shared between programmable controllers, using cyclically transmitted link relays (L) and link registers (LD).
- Data transfer function:
Programmable controllers in the same system send and receive information pertaining to contacts and registers using the high-level instructions F145 and F146.
- Remote programming function:
The programming functions of a programmable controller can be used to program other programmable controllers in the same system, and for operations such as monitoring contacts and registers. |
| S-Link module FP2-SL2 |
- The S-Link unit is used by assigning inputs (X) and outputs (Y). The inputs/outputs on the FP2 side that result from these assignments are treated as I/O addresses (S-Link I/O devices in the S-Link).
- It controls up to 2,048 remote I/Os per FP2 system.
|
|
 |
 |
|
Ethernet-LAN module FP2-ET1
|
|
The FP2 ET-LAN module enables data exchange between different types of PLCs with a vendor-independent protocol and a short processing time. TCP/IP establishes logical point-to-point communication between two devices and provides the basis for exchanging information among all areas of production. You can connect 8 Ethernet segments with each other at a transmission speed of up to 100Mbits/s. Three communication interface types are supported: 10 BASE 5, 10 BASE-T, 100 BASE-TX.
|
 |
 |
|
FP2 MEWNET-VE Link Unit FP2-VE
|
|
With the FP2 MEWNET-VE Link Unit, you can connect PLCs controlled by an FP2SH CPU to our proprietary MEWNET network in VE mode and to other manufacturers' devices in the FL-net network.
FL-net is an increasingly popular, open technology based on industrial Ethernet and endorsed by the Japan Electrical Manufacturers' Association. In contrast to standard Ethernet, FL-net guarantees transmission times for data transfer, i.e. real-time data transmission is realized by employing FA link protocol on top of UDP/IP, yielding communication with a baud rate of 10Mbps.
Maximum number of connected link units - VE mode: 99 units - FL-net mode: 254 units
|
 |
 |
|
Fieldbus Master Units for PROFIBUS DP, CANopen and DeviceNet
|
|
The expansion Fieldbus Master Units (FMU) allow you to integrate FP2 PLCs as Master into your network with a maximum degree of flexibility. The units are available for three bus systems: PROFIBUS, DeviceNet and CANopen. For each network type, ready-made function libraries are available for the programming software Control FPWIN Pro. These libraries drastically shorten the time needed to develop your applications, and consequently save valuable human resource costs.
|
|